Fire resistant power cable

First, product features and uses

This product has high fire resistance and can withstand short-circuit and short-circuit faults within a certain period of time under direct flame combustion. Therefore, it is beneficial to reduce losses in the event of fire. Low-smoke halogen-free cables are environmentally friendly cables, especially Applicable to electric power, large buildings, railways, ships and other industries that require high fire protection.


Second, product implementation standards

Q/HHTZH009.2

Fire resistance meets the requirements of GB/T19666-2005 (IEC331)


Third, the use of characteristics

1、AC rated voltage:U0/U 0.6/1kV

2, the highest long-term working temperature: flame retardant PVC insulation and sheath 70°C and 105°C; fluoroplastic insulation and sheath 200°C and 260°C; cross-linked polyethylene insulation 90°C; low-smoke halogen-free flame retardant polyolefin 70°C; low smoke zero halogen flame retardant crosslinked polyolefin 90°C and 125°C.

3, the minimum ambient temperature: flame retardant PVC sheath: fixed laying -40°C, non-fixed laying -15°C; fluoroplastic insulation and sheath: fixed laying -60°C; non-fixed laying -20°C.

4, fire resistance characteristics:

In accordance with IEC331 regulations

Flame temperature 750°C, burning time 3h, cooling time 12h, additional rated voltage, additional 3A current

Meet the requirements of GB/T19666A

Flame temperature 950-1000°C, burning time 90min, additional rated voltage 3A current

Meet the requirements of GB/T19666B

Flame temperature 750-800°C, combustion time 90min, additional rated voltage 3A current

5. The cable installation temperature is not lower than 0°C.

6. The refractory layer is between the conductor and the insulation. The insulation can be appropriately thinned. The thickness after thinning is not less than 80% of the nominal thickness.

7. Allowable bending radius recommended for laying: non-armored cable is not less than 6 times the outer diameter of the cable;

The armored cable is not less than 12 times the outer diameter of the cable;

The fluoroplastic insulation and sheathing cable is not less than 8 times the outer diameter of the cable.


Fourth, the basic model and name

model

product name

NH-VV

Flame retardant PVC insulated and sheathed fire resistant power cable

NH-FF

Fluoroplastic insulated and sheathed fire resistant power cable

NH-VDVD

Low-smoke low-halogen flame-retardant PVC insulated and sheathed fire-resistant power cable

NH-YDYD

Low-smoke, halogen-free flame-retardant polyolefin insulated and sheathed fire-resistant power cable

Note: Add 22 after armored cable model and P after shielding cable type.


Five: code name and meaning

project

Code

Description

Fire resistance

NH

Fire resistant cable A or B

Serial code

/

power cable

Insulation Materials

V

Flame retardant polyvinyl chloride

 

YD

Low-smoke halogen-free polyolefin (YDJ low-smoke halogen-free crosslinked polyolefin)

 

YJ

XLPE

 

F

Fluoroplastics are divided into 200°C and 260°C

Jacket material

V

Polyvinyl chloride, flame retardant PVC

 

F

Fluoroplastics are divided into 200°C and 260°C

 

YD

Low-smoke halogen-free polyolefin

Armored material

22

Steel tape armored PVC sheath

 

32

Steel wire armored PVC sheath


Six: main technical indicators

Performance project

unit

Technical indicators

20°C conductor DC resistance ≤ DC

Ω/km

In line with GB/T3956

Test voltage

3.5kV/5min

Insulation resistance

MΩ·km

500

Fire resistance

GB/T19666-2005 Class A or Class B

Flame retardant properties

GB/T19666-2005 Class A or Class B