Plastic insulated control cable

First, product features and uses

This product is suitable for transmission lines with automatic control or monitoring system and electrical instrument connection for AC rated voltage of 450/750V and below. The low-smoke halogen-free polyolefin has a small amount of smoke during combustion and is free of halogen acid gas, and is an environmentally-friendly cable, and is suitable for occasions with special requirements for fire protection.


Second, product implementation standards

GB/T9330-2008

Flame retardant performance test implementation of GB/T12666-2008 standard


Third, the use of characteristics

1. AC rated voltage: U0/U 450/750V.

2. the highest working temperature: polyvinyl chloride (polyethylene) insulation does not exceed 70°C, XLPE insulation 90°C, low-smoke halogen-free flame retardant polyolefin 70°C, low-smoke halogen-free flame retardant cross-linked polyolefin 90°C And 125°C two.

3. the minimum ambient temperature: PVC sheath: fixed laying -40°C, non-fixed laying -15°C

4. The cable installation temperature should not be lower than 0°C.

5. the allowable bending radius of the cable: the minimum non-armored cable is 6 times the outer diameter of the cable; the copper tape shielded or steel tape armored cable is at least 12 times the outer diameter of the cable


Fourth, the basic model and name

1. PVC insulated and sheathed control cable

KVV

Copper core PVC insulated PVC sheathed control cable

KVVP

Copper core PVC insulated and sheathed copper wire braided shielded control cable

KVVP2

Copper core PVC insulated and sheathed copper tape shielded control cable

KVV22

Copper core PVC insulated and sheathed steel tape armored control cable

KVVR

Copper core PVC insulated PVC sheathed control flexible cable

KVVRP

Copper core PVC insulated and sheathed copper wire braided shield control flexible cable

KVVP2-22

Cu core PVC insulated PVC sheathed copper tape shielded steel tape armored control cable


2. XLPE insulated PVC sheathed control cable

KYJV

Copper core XLPE insulated PVC sheathed control cable

KYJVR

Copper core XLPE insulated PVC sheathed control flexible cable

KYJVP

Copper core XLPE insulated copper wire braided screened PVC sheathed control cable

KYJVRP

Copper core XLPE insulated copper wire braided screened PVC sheathed control flexible cable

KYJVP2

Copper core XLPE insulated copper tape shielded PVC sheathed control cable

KYJVRP2

Copper core structured, XLPE insulated, copper strip screened, PVC sheathed control flexible cable

KYJV22

Copper core XLPE insulated PVC sheathed steel tape armored control cable

KYJVP22

Copper core XLPE insulated copper braided screened PVC sheathed steel tape armored control cable

KYJVP2-22

Copper core structured, XLPE insulated, copper strip screened, PVC sheathed steel tape armored control cable


3. Low-smoke, halogen-free flame-retardant polyolefin insulated and sheathed control cable

KYDYD

Copper core low smoke zero halogen flame retardant polyolefin insulated and sheathed control cable

KYDYDR

Copper core low-smoke halogen-free flame-retardant polyolefin insulation and sheath control flexible cable

KYDYDP

Copper core low-smoke halogen-free flame-retardant polyolefin insulated and sheathed copper wire braided shielded control cable

KYDYDRP

Copper core low-smoke halogen-free flame-retardant polyolefin insulated and sheathed copper wire braided shield control flexible cable

KYDYDP2

Copper core low-smoke halogen-free flame-retardant polyolefin insulated and sheathed copper tape shielded control cable

KYDYDRP2

Copper core low-smoke halogen-free flame-retardant polyolefin insulated and sheathed copper tape shielded control flexible cable

KYDYD-22

Copper core low-smoke halogen-free flame-retardant polyolefin insulated and sheathed steel tape armored control cable

KYDYDP22

Copper core low-smoke halogen-free flame-retardant polyolefin insulated and sheathed copper wire braided shielded steel tape armored control cable

KYDYDP2-22

Copper core low-smoke halogen-free flame-retardant polyolefin insulated and sheathed copper tape shielded steel tape armored control cable

Note: 1. The insulation and sheath of the basic model are YDJ low-smoke halogen-free flame-retardant cross-linked polyolefin.

2. need to add ZR before the flame retardant jacket model, the copper wire in the conductor core can be tinned.

3. If you need tinned copper wire braided shield or aluminum-plastic composite tape wrapped shield, just change the P or P2 in the model to P1 or P3.


Five: code name and meaning

project

Code

Description

Flame retardant properties

ZR

Grade A, B, C flame retardant

Serial code

K

Control Cable

Insulation Materials

V

Polyvinyl chloride, flame retardant PVC

 

Y

Polyethylene PE

 

YD

Low-smoke halogen-free polyolefin (YDJ low-smoke halogen-free crosslinked polyolefin)

 

YJ

XLPE

Jacket material

V

Polyvinyl chloride, flame retardant PVC

 

YD

Low-smoke halogen-free polyolefin

Shielding material

P

Copper wire braided shield

 

P1

Tinned copper wire shield

 

P2

Copper tape wrapped shield

 

P3

Aluminum plastic wrap shielding

Armored material

22

Steel tape armored PVC sheath

 

23

Steel tape armored polyethylene sheath

 

32

Steel wire armored PVC sheath

 

33

Steel wire armored polyethylene sheath

Conductor structure

A

Single strand conductor

 

B

7 stranded conductor

 

R

Stranded conductor


Six. main technical indicators

1. The DC resistance of the finished cable conductor (in accordance with GB/T3956) is specified in Table 3 of Appendix A.

2. The insulation resistance and the nominal thickness of the insulation meet the following requirements:

Nominal cross section(mm2)

Insulation nominal thickness(mm)

Insulation resistance (≥MΩ·km)

V、YD

YJ、Y

20℃

70℃

0.5

0.6

0.6

13

0.013

0.75

0.6

0.6

12

0.012

1.0

0.6

0.6

11

0.011

1.5

0.7

0.6

11

0.011

2.5

0.8

0.7

10

0.010

4

0.8

0.7

8.5

0.0085

6

0.8

0.7

7

0.0070

10

1.0

0.7

6.5

0.0065

3. The finished cable is subjected to AC 50Hz 3.0kV/5min voltage test without breakdown.