First. product features and uses
This product is suitable for transmitting electrical energy in power equipment and power lines with AC rated voltage of 35kV and below. XLPE insulated power cable has excellent thermal-mechanical performance, excellent electrical and chemical resistance, and it also has cable weight. Light, convenient to transport, not subject to drop restrictions, etc., it is widely used in metallurgical, electric power, petrochemical enterprises and urban power grid construction.
Second. product implementation standards
GB/T12706 equivalent to adopt IEC60502 standard
Flame retardant and fire resistance test is carried out according to GB/T12666-2008 standard
Third. the use of characteristics
Use characteristics | XLPE insulation | |
Rated voltageU0/U | 0.6/1、1.8/3、3.6/6、6/6、6/10、8.7/10、8.7/15、12/20、21/35、26/35 | |
Maximum operating temperature of the conductor | 90℃ | |
Short circuit temperature (lasting 5S) | ≤250℃ | |
Ambient temperature during laying | ≥0°C (preheating is required below 0°C) | |
Allowable bending radius when laying | Single core cable | Not less than 10 times the outer diameter of the cable |
Multi-core cable | Not less than 15 times the outer diameter of the cable | |
Flame retardant properties | Comply with GB/T19666-2005A, B or C (IEC332-3) |
Fourth. the basic model and name
model | product name |
YJV | Copper core XLPE insulated PVC sheathed power cable |
YJVD | Copper core XLPE insulated PVC sheathed low-smoke low-halogen flame-retardant power cable |
YJE | Copper core XLPE insulated polyolefin sheathed low-smoke low-halogen flame-retardant power cable |
YJV22 | Copper core XLPE insulated steel tape armored PVC sheathed power cable |
YJV23 | Copper core XLPE insulated steel tape armored PE sheathed power cable |
YJV32 | Copper core XLPE insulated thin steel wire armored PVC sheathed power cable |
YJV33 | Copper core XLPE insulated thin steel wire armored PE sheathed power cable |
Note: The aluminum core cable adds L to the model number, and the flame retardant cable adds ZR to the model number.
V. Code name and meaning
Code | Code meaning |
- | Non flame retardant |
ZR | Flame retardant: divided into three grades A, B and C |
insulation |
|
YJ | XLPE |
E | Low-smoke halogen-free flame retardant polyolefin |
jacket |
|
V | Polyvinyl chloride |
VD | Low-smoke low-halogen flame retardant PVC |
Armoured |
|
2 | Double steel wire armor |
3 | Thin steel wire armor |
4 | Thick steel wire armor |
Six. main technical indicators:
1. The DC resistance of the finished cable conductor (according to the provisions of GB/T3956), refer to Table 1 of Appendix A;
2. Power frequency voltage test:
U0 is 3.6kV and below cable: 2.5U0+2/5min without breakdown;
U0 is a cable of 3.6kV or more to 18kV: 3.5U0/5min without breakdown;
U0 is a cable of 18kV or more to 26kV: 3.5U0/5min or 2.5U0/30min.
3. Partial discharge test: The discharge amount is not more than 10pc under 1.73U0.