First. product features and uses
This product is suitable for transmission of electrical energy in AC equipment with rated voltage of 0.6/1kV and power line. Low-smoke and halogen-free insulated and sheathed cables are environmentally friendly cables and are suitable for use in high-rise buildings, railways and other industries where fire protection and other special requirements are required.
Second. product implementation standards
GB/T12706 equivalent to adopt IEC60502 standard
Flame-retardant properties test implementation of GB/T12666-2008 standard
Third. the use of characteristics
Use characteristics | PVC insulation | |
Rated voltage U0/U | 0.6/1kV | |
Maximum operating temperature of the conductor | 70℃ | |
Short circuit temperature (up to 5s last) | ≤160℃ | |
Ambient temperature during laying | ≥0°C (preheating is required below 0°C) | |
Allowable bending radius when laying | Single core cable | Not less than 20 times the outer diameter of the cable |
Multi-core cable | Not less than 15 times the outer diameter of the cable | |
Flame retardant properties | Comply with GB/T19666-2005A or B (IEC332-3) |
Fourth. the basic model and name
model | product name |
VV | PVC insulated PVC sheathed power cable |
VV22 | PVC insulated steel tape armored PVC sheathed power cable |
VV32 | PVC insulated steel wire armored PVC sheathed power cable |
ZR-VV | PVC insulated PVC sheathed flame retardant power cable |
ZR-VV22 | PVC insulated steel tape armored PVC sheathed flame-retardant power cable |
ZR-VDVD | PVC insulated and PVC sheathed low-smoke low-halogen flame-retardant power cable |
ZR-YDYD | Low-smoke halogen-free polyolefin insulated and sheathed power cable |
V. Code name and meaning
Code | Code meaning |
Flame retardant properties |
|
- | Non flame retardant |
ZR | Flame retardant: divided into three grades A, B and C |
NH | Fire resistant cable |
insulation |
|
V | PVC PVC |
jacket |
|
V | PVC PVC |
YD | Low-pressure halogen-free flame retardant polyolefin |
VD | Low-smoke low-halogen flame retardant PVC |
Armoured |
|
22 | Double steel belt armor |
32 | Thin steel wire armor |
42 | Thick steel wire armor |
Six. main technical indicators
1. DC resistance of finished cable conductor (in accordance with GB/T3956);
2. Power frequency voltage test: AC 50Hz 3.5kV/5min does not breakdown.