First. product features and uses
This product is suitable for power supply cable or electrical connection of AC rated voltage 0.6/1kV and below. The product has strong voltage withstand resistance, can withstand the pulse voltage during frequency conversion, the cable has good shielding and effectively eliminates Electromagnetic interference reduces the noise of the variable frequency motor and ensures stable operation of the system. Widely used in metallurgy, electric power, petrochemical and other industries.
Second. product implementation standards
Q/HHTZH006
Flame retardant and fire resistance test is carried out according to GB/T12666-2008 standard
Third. the use of characteristics
1. AC rated voltage: U0/U 0.6/1kV;
The highest working temperature: silicone rubber insulation 180°C, fluorine 46 insulation 200°C and 260°C;
PVC insulation 70°C cross-linked polyethylene 90°C;
Minimum ambient temperature: The ambient temperature when laying the cable should not be lower than -40°C; the PVC sheathed cable should not be lower than 0°C.
2. The cable installation temperature should not be lower than -25°C.
3. The allowable bending radius of the cable: the minimum cable is 10 times the outer diameter of the cable.
Fourth. the basic model and name
model | name |
BPGGP | Silicone rubber insulated and sheathed copper wire braided shielded high temperature variable frequency power cable. |
BPGGP2 | Silicone rubber insulated and sheathed copper tape wrapped shielded high temperature variable frequency power cable. |
BPGGPP2 | Silicone rubber insulated and sheathed copper wire braided copper tape wrapped shielded high temperature resistant variable frequency power cable. |
BPGGP3 | Silicone rubber insulated and sheathed aluminum polyester composite film wrapped shielded high temperature resistant variable frequency power cable. |
BPGVFP | Silicone rubber insulated nitrile sheathed copper wire braided shielded high temperature resistant variable frequency power cable. |
BPGVFP2 | Silicone rubber insulated nitrile sheathed copper tape wrapped shielded high temperature resistant variable frequency power cable. |
BPGVFPP2 | Silicone rubber insulated nitrile sheathed copper wire braided copper tape wrapped shielded high temperature resistant variable frequency power cable. |
BPGVFP3 | Silicone rubber insulated nitrile sheathed aluminum polyester composite film wrapped shielded high temperature resistant variable frequency power cable. |
BPFFP | Fluorine 46 insulated and sheathed copper wire braided shielded high temperature variable frequency power cable. |
BPFFP2 | Fluoride 46 insulated and sheathed copper tape wrapped shielded high temperature variable frequency power cable. |
BPFFPP2 | Fluorine 46 insulated and sheathed copper wire braided copper tape wrapped shielded high temperature resistant variable frequency power cable |
BPFFP3 | Fluoride 46 insulated and sheathed aluminum polyester composite film wrapped shielded high temperature resistant variable frequency power cable. |
BPVVP | PVC insulated and sheathed copper wire braided shielded variable frequency power cable. |
BPVVP2 | PVC insulated and sheathed copper tape wrapped shielded variable frequency power cable. |
BPVVPP2 | PVC insulated and sheathed copper wire braided copper tape wrapped shielded variable frequency power cable. |
BPVVP3 | Polyvinyl chloride insulated and sheathed aluminum polyester composite film wrapped shielded variable frequency power cable. |
BPYJVP | XLPE insulated PVC sheathed copper wire braided shielded variable frequency power cable. |
BPYJVP2 | XLPE insulated PVC sheathed copper tape wrapped shielded variable frequency power cable. |
BPYJVPP2 | XLPE insulated PVC sheathed copper wire braided copper tape wrapped shielded variable frequency power cable. |
BPYJVP3 | XLPE insulated PVC sheathed aluminum polyester composite film wrapped shielded variable frequency power cable. |
Note: The copper wire in the conductor core can be tinned, the flame retardant cable type is added with ZR, and the soft structure cable is added with R.
V. Code name and meaning
Code | Code meaning |
BP | Variable frequency power cable |
Copper conductor | Omit |
G | Silicone rubber insulation or sheath |
F | F46 insulation or sheath |
V | PVC insulation or sheath |
YJ | XLPE insulation |
VF | Nitrile sheath |
P(P1) | Copper braided shield (tinned braided shield) |
P2 | Copper tape wrapped shield |
P3 | Aluminum polyester composite film wrapped shielding |
PP2 | Copper wire braided copper tape wrapped shield |
Six. main technical indicators
1. The DC resistance of the finished cable conductor (in accordance with GB/T3956) refers to Appendix A and Table 2.
2. The insulation resistance (20 °C) of the finished cable should be not less than 100 MΩ·km for fluoroplastic and silicone rubber insulation.
PVC insulation should be no less than 50 MΩ/·km.
3. The finished cable is subjected to AC 50Hz 3.5kV/5min voltage test without breakdown.
4, shield transmission impedance
The transmission impedance of the cable at 100 MHz is equal to or less than 100 Ω/m.
The ideal shielding rejection factor for the cable is equal to or less than 0.7.